General Description
The A1413 type station is a programmable, automatic, electromechanical high-voltage generator.
The unit is particularly well-suited for use with a test cage.
Main Features
- High Voltage testing at 15kVAC, 20kVAC, 30kVAC, 40kVAC up to 100kVAC max (depending on the model)
- High Voltage Setting via Programming
- Gradual Rise/Decrease with Step Management
- Automatic and Manual Operating Modes
- Digital Display of High Voltage Measurement on Touchscreen Control Panel
- Digital Display of Leakage Current Measurement on Touchscreen Control Panel
- Programming and Messaging Display on Touchscreen Control Panel
- Programmable Tripping Threshold (1 to 100mA depending on the version)
- In case of fault : tripping, audible and visual alarm
- Test Program Management and Test Recording
- Safety Start-up Procedure with management of a “cage” safety contact and a “grounding stick” safety contact
Technical specifications
| Power Supply | 230 V / 50 Hz + ground |
| Presentation | Electrical cabinet |
| High-voltage AC test
Voltage setting and measurement
Leakage current measurement Trip-out threshold Test duration Ramp-up speed Ground reference Test start mode Results recording |
Adjustable from 15KVAC / 20KVAC / 30KVAC / 40KVAC / up to 100KVAC max depending on the model chosen Digital display with accuracy as a percentage of the value (2.5 to 3.5%) or a percentage of the range (1.5 to 2.5%) Digital display with accuracy as a percentage of the value (2.5 to 3.5%) or a percentage of the range (1.5 to 2.5%) 1 à 100mA selon version par programmation Programmable Programmable ( ex. 500V/s) Yes (version possible with 2 opposing high-voltage sources) Cycle start button with mandatory return to “0” High Voltage Results with traceability elements (USB transfer) |
Items supplied with the unit:
- User manual
- Verification report with COFRAC connection certificate
Available accessories :
- Test cables
- Fault simulation box
- Test cages
- Grounding stick
- …