Single high-voltage substation ≤ 10KV type A518

General description

A887b new

The A518 unit is a simple high-voltage generator with an electromechanical design.

The device is particularly suitable for manual use with test clamps or test guns, or for use in an automatic system.

 

 

 

Main features

  • High voltage test at 3KVAC, 5KVAC or 10KVAC max (depending on model selected)
  • High voltage adjustment via rotary knob on front panel
  • Analogue display of high voltage measurement on front panel
  • Fixed trip threshold set at factory (5 to 25mA as required)
  • In the event of a fault : disconnection, audible and visual alarm

Technical specifications

Power Supply 230 V / 50 Hz + ground
Presentation standard box 19″
High-voltage AC test

Voltage adjustment and measurement

 

Leakage current measurement

Tripping threshold

Test duration

Burn function

Ground reference

Test launch mode

Results recording

 

Adjustable up to 3KVAC / 5KVAC / 10KVAC max depending on the model chosen

Digital display with accuracy as a percentage of the value (2.5 to 3.5%) or a percentage of the range (1.5 to 2.5%)

Without

5 to 25 mA fixed (factory setting)

Electromechanical timer option

Without

Yes

Press and hold the remote control input (gun, push button or system contact)

Without

Items supplied with the unit :

  • User manual
  • Verification report with COFRAC connection certification

Available accessories :

  • Test cables
  • Test guns
  • Fault simulation box
  • Test cages